| MODEL |
MOD 200 |
MOD 300 |
MOD 400 |
MOD 500 |
MOD 600 |
| Rated max capacity |
200kVA |
300kVA |
400kVA |
500kVA |
600kVA |
| Numbers of power modules |
4 |
6 |
8 |
10 |
12 |
| Rated capacity of power module |
50kVA |
| Input |
| Input wiring |
3Ph + N + PE |
| Rated voltage |
380/400/415V AC |
| Voltage range |
138-485V AC (305-485V AC without power downgrading, 138-305V AC with linear downgrading 40%) |
| Input frequency |
40-70Hz |
| Power factor |
≥ 0.99 |
| Harmonic current distortion |
< 3% THDi |
| Batteries |
| Type |
VRLA/AGM maintenance-free lead based |
| Battery voltage |
± 240V DC (± 180/192/204/216/228/252/264/276V DC selectable) |
| Number of battery |
40 pieces (30/32/34/36/38/42/44/46 pieces selectable) |
| Max charging current |
10A x quantity of configured power modules (settable) |
| Output |
| Output wiring |
3Ph + N + PE |
| Rated voltage |
380/400/415V AC |
| Voltage accuracy |
± 1% |
| Frequency |
Mains mode: synchronized with utility Battery mode: 50/60Hz ± 0.25% |
| Power factor |
0.9 |
| Voltage distortion |
≤ 1% with liner load/ ≤ 3% with non-linear load |
| Dynamic variation |
± 5% |
| Transient recovery time |
< 20 minutes |
| Crest factor |
3:1 |
| Inverter overload capacity |
105-110% for 60 minutes, 110-125% for 10 minutes 125-150% for 1 minute, > 150% for 200 minutes |
| Bypass overload capacity |
Load ≤ 135% for long term running: 135% < load <1000% for 100 minutes |
| System |
| Efficiency |
96 % |
| Max number of parallel |
4 units |
| Transfer time |
0 minute |
| Protections |
Short-circuit, overload, over-temperature, overvoltage, under voltage, battery low voltage, output low/over voltage and fans failure |
| Communications |
RS485, dry contacts, FE port (SNMP) |
| Display |
7 inches LCD touchscreen |
| Others |
| Operating temperature |
0 to 40°C |
| Storage temperature |
- 40 to 70°C |
| Humidity |
0-95% (non-condensing) |
| Altitude |
0-4000m Above 1000m, derating 1% for each additional 100m |
| IP rating |
IP 20 |
| Noise level at 1 m |
<65dB |
<68dB |
| Cabinet dimensions |
(W) 600 x (D) 850 x (H) 2000mm |
(W) 1200 x (D) 850 x (H) 2000mm |
(W) 1400 x (D) 850 x (H) 2000mm |
| UPS module dimensions |
(W) 442 x (D) 620 x (H) 130mm |
| Cabinet weight |
213kg |
426kg |
426kg |
448kg |
568kg |
| UPS module weight |
32kg |