Product Details
Model Number: EA800 6-10KVA(1:1) / 10-30KVA (3:1)
Key Specifications/Special Features:
FeaturesSingle / single-phase, three / single-phase models with on-line double convesition technologyDSP (Digital Signal Processors) technologySuitable for all kinds of loads (resistive, inductive and non-linear loads etc)High overload capability (up to 150%)Bypass dual DSP control design to enhance more reliability
Supports dual input, hot standby in series
Redundant & parallelable with advanced parallel current-sharing control technology
Cold start and mains start function
High charging capability: 2 A / 4 A / 6 A / 8 A / 10 A / 12 A selectable (standard), 14 A / 16 A / 18 A / 20 A / 22 A / 24 A selectable (options)
Standard configuration with output isolation transformer
Superior protection (surgers, short-circuit, overvoltages, undervoltages, overcharge, reverse connection protection etc)
Advanced communications (RS232 and USB ports (standard), SNMP, dry contacts and RS485 (options))
Other options (parallel kits, input isolation transformer, bypass isolation transformer and harmonic suppressor)
| MODEL |
EA806 (1:1) |
EA810 (1:1) |
EA810 (3:1) |
EA815 (3:1) |
EA820 (3:1) |
EA830 (3:1) |
|
| Capacity |
6 KVA 4800 W |
10 KVA 8 KW |
10 KVA 8 KW |
15 KVA 12 KW |
20 KVA 16 KW |
30 KVA 24 KW |
|
| INPUT |
|
| Rated voltage |
220 / 230 / 240 Vac (1φ+N+PE) |
380 / 400 / 415 Vac(3φ+N+PE) |
|
| Voltage range |
165 ~ 275 Vac |
285 ~ 475 Vac |
|
| Rated frequency |
50 Hz / 60 Hz |
|
| Frequency range |
40 ~ 70 Hz |
|
| Frequency tracking range |
± 5% Hz |
|
| BYPASS |
|
| Rated voltage |
220 / 230 / 240 Vac(1φ+N+PE) |
|
| Overload capability |
Load current < 150% rated current: long time running 150% ≤ load current < 200%: 1 min 200% rated current ≤ load current: 200ms |
|
|
BATTERIES
|
|
| Battery voltage |
192 Vdc |
|
| Battery type |
VRLA AGM maintenance-free lead based |
|
| Number of battery |
12 V * 16 pcs |
|
| Charging voltage |
220 Vdc |
|
| EOD |
168 Vdc |
|
| Charging current |
Default 8 A (2 A / 4 A / 6 A / 8 A / 10 A / 12 A selectable) |
|
| OUTPUT |
|
| Rated voltage |
220 / 230 / 240 Vac(1φ+N+PE) |
|
| Power factor |
0.8 |
|
| Waveform |
Sinusoidal |
|
| Rated frequency |
50 Hz / 60 Hz (settable) |
|
| Frequency precision |
Mains mode: track bypass input in the state of synchronization Battery mode: 50 / 60 ± 0.1 Hz |
|
| Voltage precision |
± 1% |
|
| Recoverytime of transientvoltage |
< 20 ms |
|
| Crest factor |
3:1 |
|
| THDV |
≤ 3% (linear load); ≤ 6% (non-linear load) |
|
| Overload capability |
Load ≤ 105%: long time running; 105% < load ≤ 125%: transfer to bypass in 10 mins; 125% < load ≤ 150%: transfer to bypass in 1 min 150% < load ≤ 200%: transfer to bypass in 200 ms 200%< load: transfer to bypass in 100 ms |
|
| OTHERS |
|
| Transfer time |
0 ms |
|
| Protections |
Short-circuit – overload – overvoltage - undervoltage - low battery - overtemperature |
|
| Communications |
RS232 / USB (standard); RS485 / SNMP / dry contacts (optional) |
|
| Operating temperature |
0 ~ 40℃ |
|
| Storage temperature |
-25℃ ~ 55℃ (without batteries); |
|
| Relative humidity |
0 ~ 95% (non-condensing) |
|
| Operating altitude |
≤ 1000 m (derating 1% for each additional 100 m) |
|
| Noise level |
< 60 dB (at 1 m) |
|
| MTBF |
MTBF > 200000 h |
|
| MTTR |
MTTR < 0.5 h |
|
| IP rating |
IP20 |
|
Dimensions (W×D×H) (mm) |
210 x 585 x 590 |
310 x 600 x 880 |
400 x 815 x 1100 |
|
| Net weight (kg) |
54 |
96 |
130 |
201 |
230 |
277 |
| Gross weight (kg) |
64 |
108 |
142 |
216 |
245 |
292 |
Shipping Information:
-
FOB Port:
Shenzhen
-
Lead Time:
20
-
25
days
Main Export Markets:
- Asia
- Australasia
- Central/South America
- Eastern Europe
- Mid East/Africa
- North America
- Western Europe
Download more information about this product